Directory of Listed Products
 
 

Go to Directory Page

 

 
  FIRE LISTING PROGRAM  
  Class: Fire Resistant Air Duct Insulation  
       
  Customer: CL4 Inc.   
  Location: London, ON  
       
  Listing No.: F405-1   
  Effective Date: January 6, 2012  
  Last Revised: January 6, 2012  
  Expires: N/A  
       
  Standards: ISO 6944 "Fire resistance tests - Ventilation ducts"  
       
  Product: CL4FIRE™ Foil Encapsulated Ductwrap Insulation  
       
  Markings: Each container of the subject product, as delivered to the customer, is suitably marked using Permanent label stock with permanent adhesive with the following:

  1. QAI logo with ‘c’ and ‘us’ indicator
  2. Manufacturers name or trademark
  3. City and state of manufacture
  4. Model/Listing number or product description
  5. QAI file number (F405)
  6. Traceability Information: date of manufacture or serial number
  7. Standards: See above
  8. Applicable Ratings: See below
 
       
  Models:

Design Number:

Product:

Formula Model #:

# of Layers:

Thickness:

Density:

*Rating:

F405-1B1.5-FRD-60

Foil Encapsulated Duct Wrap Insulation

CL4FIRE™ ‘Blue’ Label

1

1-1/2”

8 pcf

1 Hour

F405-1B1.5-FRD-120

1

1-1/2”

8 pcf

2 Hour

F405-1R1.5-FRD-60

CL4FIRE™ ‘Red’ Label

1

1-1/2”

6 pcf

1 Hour

F405-1R1.5-FRD-120

 

1

1-1/2”

6 pcf

2 Hour

*Note - 1 Hour rating is with seams snuggly butted.  2 hour rating is with a 3" overlap at seams.

Product Assembly:

Maximum Size of Ventilation Air Duct System

  • Maximum 13,316 sq. cm. (2064 sq. inch) duct

  • Maximum single dimension of 2184mm (86")  

  • Ductwork can be Rectangular, Square, or Round Air Duct

  • Complying with Sheet Metal and Air Conditioning Contractors' National Association (SMACNA) requirements

Support Rods & Cradles

 Hanging supports must be installed per SMACNA guidelines with the following:

  • Minimum 12mm (1/2”) steel threaded rod with either of the following:

  • Steel angle - 51mm x 51mm  x 5mm (2” x 2” x 3/16”)

  • Unistrut P2000 channel - 51mm x 5mm (2” x 3/16”)

  • Support rods to be anchored to concrete using pass thru method with a nut & washer on the top of the concrete slab, or by using suitable carbon or stainless steel masonry anchors penetrating a minimum 50mm (2”) depth into the concrete slab.

  • No additional protection is required for hanger systems

NOTE: If desired, it is acceptable to encase the cradle support assembly along with the duct within the *CL4Fire (blue) or *CL4FIRE (red) insulation (i.e.: cocoon wrap) during the installation. A slit is allowed in the duct wrap in order to position around the threaded rod. Slit must be repaired and sealed using a minimum depth of 6mm sealant with a bead also placed around the circumference of the support rod.

Fastening Methods

Standard Banding Method

  • All cut ends of insulation to be repaired with aluminum tape

  • Seams installed either by snugly fitting the seams together or by sealing any maximum ¼” wide voids in the insulation seams with minimum of ½” depth of sealant

  • Pinning is required on the underside of CL4FIRE exposed ductwork joints for ducts.  Pins are required within 1 ½” from both sides of CL4FIRE longitudinal seam. 

  • Additional pins may be added to increase the integrity of the installation

  • Center pins between steel banding with a 12” maximum distance between pins on the bottom of the ductwork and maximum of 12” between the side of the duct and the first row of pins.  Note: Maximum 18” space is allowed between the edge of the duct and the first row of pins when not located on the bottom side of a horizontal duct

 

 

 

 
 

 

 

 

                               

Figure 1: Pinned and Banned Detail

Detail when longitudinal seam located on bottom of duct:

  • 1-1/2” long x 1/8” copper coated steel insulation pins or Cup-Head Weldpins® required to be stud welded on bottom side of a horizontal duct. Pins are to be located a maximum 8” from edge of duct and on maximum 12” centers in 2 rows per 24” wide CL4FIRE installed section. Pins are centered between banding on each individual wrap section – See standard installation method pinning detail).

Note: No pins are required between the circumference seaming bands other than at the longitudinal joint. Additional pins may be installed to enhance the integrity of the CL4Fire duct wrap installation.

  • CL4FIRE insulation to be impaled on pins and held in place with speed clips

  • Alternatively, ductwrap may be installed prior to pinning with Cup-Head Weldpins®.

  • CL4FIRE ductwrap is held in place by banding the insulation around the duct approx. 1½” on both sides of the seam and in the center of the CL4FIRE wrap layer.

  • No aluminum tape is required on seams, but it may be used for cosmetic reasons if desired.

 

Pinned Only Method

  • Requires one (1) layer of CL4FIRE ductwrap overlapped a minimum of 3” at the seams for up to a 2-hour ventilation air duct systems and snugly butted at the seams for a 1-hour ventilation air duct systems.

  • All cut ends of insulation to be repaired with aluminum tape.

  • Seams are installed snugly fitted or by sealing any max. ¼” wide voids in the seams with a minimum of ½” depth of the approved sealants (refer to the Raw Materials Section).

Figure 2: Pinned only Detail

 

  • 1-1/2” long x 1/8” copper coated steel insulation pins or Cup-Head Weldpins®

  • Pins are required on all sides of duct at max. 12” centers – max. 6” pin-free space from edge of ductwork is allowed.

  • Install Cup-Head Weldpins® on both sides of the CL4FIRE ductwrap seam. Cup-Head Weldpins® must be located 3” apart (1½” on either side of the CL4FIRE ductwrap seams).

  • Longitudinal seams of the outside layer of wrap material require CL4FIRE Ductwrap Pinning Only pinning at max 12” centers and max. 2” from each edge the ductwrap material.

  • No aluminum tape is required on seams, but it may be used for cosmetic reasons if desired. 

Gypsum Shaft Transition (if required)

  • Should a transition be required from a gypsum shaft system to a CL4FIRE Fire Protection Thermal Insulation installation the annular space around the duct and the shaft must be filled with a minimum of 102mm (4”) depth of CL4FIRE insulation and topped with a 6mm (1/4”) depth of sealant flush with the surface of the gypsum. (refer to the raw materials section in the F405-1 - Edition 1 - CL4 Inc. - Evaluation Report - Jan 6, 2012 for approved sealants)

 

1-Hour Fire-Rated Ductwrap System

The following CL4FIRETM ventilation air duct fire protection thermal insulation system achieves a 1 hour fire resistance rating:

  • One-layer of CL4FIRETM ‘Blue’ Label – 8 PCF - 1-1/2”

    • System Design Number: F405-1B1.5-FRD-60

  • One-layer of CL4FIRETM ‘Red’ Label – 6 PCF - 1-1/2”

    • System Design Number: F405-1R1.5-FRD-120

 

Adobe Systems

Single Layer System with butt joint Installation

The steel duct shall be wrapped using tightly butted seams (minimum 1/2” total joint compression so 24” wide wrap installs to a maximum dimension of 23 ½”) or alternatively using any 2-hour listed system installation with either CL4FIRETM Standard or Pinned Only fastening method (shown above). All cut edges and ends shall be sealed with 76 mm (3”) wide pressure sensitive aluminum foil tape.

 

2-Hour Fire-Rated Ductwrap System

The following CL4FIRETM ventilation air duct fire protection thermal insulation systems achieve a 2 hour fire resistance rating:

  • One-layer of CL4FIRETM ‘Blue’ Label – 8 PCF - 1-1/2”

    • System Design Number: F405-1B1.5-FRD-120

  • One-layer of CL4FIRETM ‘Red’ Label – 6 PCF - 1-1/2”

    • System Design Number: F405-1R1.5-FRD-120

Adobe Systems

Adobe Systems

Single Layer System with 76mm (3”) overlap Installation

Single Layer System with butted joints and 152mm (6”) Collar over circumferential butted seam Installation

The steel duct shall be wrapped with any of the above noted 2 hour duct wrap systems  installed in a telescope, checkerboard, or butt-joint-and-152mm (6”) wide collar, with 76 mm (3”) transverse and longitudinal overlaps, in accordance with the manufacturer's installation instructions.  Product can be fastened with either CL4FIRETM Standard or Pinned Only fastening method (shown above). All cut edges and ends shall be sealed with 76 mm (3”) wide pressure sensitive aluminum foil tape.

Note: When encountering ductwork flanges using the butt seam and collar method it is not required to have the base layer of CL4FIRE insulation cover the top of the flange. It is only required that ductwork flange locations have the base layer of CL4FIRE insulation snugly butted against both sides of the flange and the 152mm wide CL4FIRE collar installed over the flange.

 

CL4FIRE Ductwrap ‘2 or 3’ Sided installation:

Pinning Only Method

 

 
 

 

 

 

 

 

Installation

  • Requires the  CL4FIRE ductwrap insulation to be installed in accordance with the instructions shown in ‘Pinning Only’ Method

  • Duct to be located a maximum of 4” from the floor or wall assembly.

Fastening

  • Install Pinning only pins (or alternatively pin both sides of seam as outlined in CL4FIRE ‘Pinning Only’ Method) on exposed sides of duct and install CL4FIRE insulation using instructions shown in ‘Pinning Only’ Method.

  • Overlap both layers of CL4FIRE  ductwrap insulation over concrete by minimum of 3” and fasten using min 1 ¼” OD fender washers over a minimum ¼” diameter steel concrete anchor inserted a minimum of 1 ½” into concrete slab spaced a maximum of 8” apart.

Banding Method

 

 
 


Installation

  • Requires the  CL4FIRE ductwrap insulation to be installed in accordance with the instructions shown in ‘Standard Banding’ Method

  • Duct to be located a maximum of 4” from the floor or wall assembly.

Fastening  

  • Install pins on exposed sides of duct (if required) and install CL4FIRE insulation using instructions shown in CL4FIRE ‘Standard Banding’ Method.

  • Overlap CL4FIRE insulation over the concrete by a minimum of 3”.

  • Anchor with a continuous length of min. 3/16” x 1 ½” wide steel flat bar over flared ends of the wrap material and fasten using min. 1 ¼” OD fender washers over a minimum ¼” diameter steel concrete anchors inserted a minimum of 1 ½” into the concrete slab spaced a maximum of 8” apart.

  • Banding to be installed over the wrapped duct with ends looped around the steel flat bars, tightened and clipped as required.

  • CL4FIRE fire protection thermal insulation is to be installed essentially to the requirements of CL4FIRE ‘Standard Banding’ Method

CL4FIRE Ductwrap through wall penetration:

  1. Floor or Wall Assemblies:
  2. Code conforming 1 or 2-hour floor or wall assembly.  Minimum 4 ½” thick lightweight or normal weight concrete, 8” thick concrete block (filled or unfilled), 1 or 2 hour gypsum wall assembly with framed opening, 1 or 2 hour gypsum ceiling / wood floor assembly with framed opening.
  3. Penetrating Item:
  4.  

    Rectangular or Round #26 gauge or thicker steel air duct (as described in Maximum Size of Ventilation Air Duct System)

  5. Wall Firestop Insulation:
  6. Minimum 4” thickness of CL4FIRE fire protection thermal insulation, or mineral wool insulation tightly compressed into concrete opening, recessed ¼” from the top and flushes with the bottom of a gypsum ceiling / wood floor assembly, or recessed ¼” from both sides of a concrete or framed gypsum wall assembly.
  7. Firestop Sealant:
  8. Firestop Sealant installed a minimum of ¼” deep flush with the top surface of a floor assembly or both sides of a wall assembly.  Installation can consist of one of the approved caulking products (refer to the raw materials section in the F405-1 - Edition 1 - CL4 Inc. - Evaluation Report - Jan 6, 2012).
  9. Duct Insulation:
  10. Duct must be wrapped with CL4FIRE insulation through the opening or the bare duct can be wrapped with CL4FIRE insulation abutting both sides of firestop assembly.
 
 
       
  Note:

Refer to QAI evaluation report F405-1 and the applicable test reports for test assembly configurations used for fire endurance testing.    

Final acceptance of the product in the intended application is to be determined by the authority having jurisdiction (AHJ).

 
 
 
 
  The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.

No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.

Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.

 
   

Copyright QAI Laboratories, 2011