Directory of Listed Products
 
 

Go to Directory Page

 

 
  FIRE DOOR LISTING PROGRAM  
  Class: Fire Door Slabs  
       
  Customer: BASF SE  
  Location:

Frankenthal, Germany

 
       
  Listing No.: F411-1  
  Effective Date: October 12, 2012  
  Last Revised: February 15, 2013  
  Expires: N/A  
       
  Standards:

CAN/ULC S104

Standard Method for Fire Tests of Door Assemblies

UL10 (b)

Fire Tests of Doors Assemblies

UL10 (c)

Fire Tests of Doors Assemblies (Category “B”)

NFPA-252

Standard Methods of Fire Tests of Door Assemblies

UBC-7-2 (1994)

Uniform Building Code

UBC-7-2 (1997)

Uniform Building Code

ASTM E2074

Standard Test Method for Fire Tests of Door Assemblies, Including Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies

 
       
  Product: 45 min Rate Arched Top Fire Door Slabs  
       
  Markings: Marking:
Each container of the subject product, as delivered to the customer, is suitably marked using Permanent label stock with permanent adhesive with the following:

  1. QAI logo with ‘c’ and ‘us’ indicator
  2. Manufacturers name or trademark
  3. City and state of manufacture
  4. Model/Listing number or product description
  5. QAI file number (F411)
  6. Traceability Information: date of manufacture or serial number

Marking Method:

Permanent label stock fastened with pins or permanent adhesive.   

 
       
  Models:

SWING-TYPE FIRE DOOR SLABS:  

General Information: 

These door slabs systems are categorized as Category “A” door slabs.  These door slabs systems have been evaluated without an edge-sealing system between the door and frame.  These door slabs systems have been evaluated with a sealing system (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.

Meeting edges of pairs do not require an astragal but a Listed astragal may be added to any pair of doors as long as the astragal is rated at an equivalent or greater fire resistance. 

These door slabs systems are eligible for use in any Category “C’ – Standard Frame.  These doors may also be installed in frames listed for Category “C” – Proprietary in accordance with the frame manufacturers’ individual listing.

These door slabs systems are eligible to bear the “S” (for Smoke & Draft Control assemblies) if a listed Category “H” – Smoke and Draft Gasket has been applied to the assembly.  Please refer to the individual gasket manufacturers’ Category “H” listings.

All door slabs systems listed below have been evaluated and tested to comply with the following standards CAN/ULC S104, UL 10(c), UBC 7-2 (1997) Part 1, NFPA 252 and ASTM E2074, “Standard Method of Fire Tests of Door Assemblies” (Positive Pressure) and CAN/ULC S104, UL 10(b), UBC 7-2 (1994), and NFPA 252, " Standard Method of Fire Tests of Door Assemblies” (Neutral Pressure), including hose stream.

Doors slab systems used in neutral pressure applications may not require the use of intumescent materials regarding the edge sealing between the perimeter of the door and the frame, smoke gasketing, or a combination thereof.  Options include frame mounting the intumescent and/or smoke gasketing, mortising the intumescent into the door perimeter, concealing the intumescent with the stile(s), or a combination of these methods.

Doors labeled for positive pressure applications must include installation instructions to be furnished by the door labeler.  Unless otherwise noted in the door’s installation instructions, all intumescent materials and smoke/draft control gasketing used in the assembly are to be installed per their respective manufacturers’ instructions.

45-Minute Arched Top Laminated Core Panel Fire Door Slabs: 

  • Category “A” Doors – No additional edge-sealing system required

  • Composite continuous core type

  • Flush or Recessed Panel Door

  • Integrated edge seal; inlaid in the door slab (Edge seal is not required for Neutral Pressure Assemblies)

Core Materials: 

Proprietary BASF Laminated Core:

Limitations:

Maximum Sizes: 

Minimum Slab Thickness  1-3/4”

Single Swing                  

  • 3’6” wide by 8’0” high

Core Options:          

  • Single Layer of SW 60-1 Core

Temperature rise:  

  • @30 min = 250°F MAX where lites do not exceed 100 in˛      

  •  
           
      Note:

    Refer to QAI evaluation report F411-1 and the applicable test reports for test assembly configurations used for fire endurance testing.    

    Final acceptance of the product in the intended application is to be determined by the authority having jurisdiction (AHJ).

     
     
     
     
      The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.

    No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.

    Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.

     
       