Directory of Listed Products
 
 

 

 
  FACTORY CONSTRUCTED BUILDINGS AND STRUCTURES LISTING PROGRAM  
  Class:

Relocatable Commercial/Industrial Structures

 
       
  Customer: Mobilfab Inc.  
  Location: Pointe-Aux-Trembles, QC  
       
  Listing No.: REC610-1  
  Effective Date: Aug 2, 2013  
  Last Revised: Aug 2, 2013  
  Expires: N/A  
       
  Standards:

CSA A277 "Procedure for Factory Certification of Buildings"

 

CSA C22.1 "Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations"

 

Alberta Building Code, Part 9 & 10

 

National Building Code of Canada, Part 9

 

National Plumbing Code of Canada

 

Standards above as provincially amended by Alberta. Jurisdictions may require structures to comply with municipal and/or provincial codes and standards in lieu of the national codes and standards.

 
       
  Product: Relocatable Commercial/Industrial Structures  
       
  Markings:

All markings must be permanent and visible after installation. 

1. The specification nameplate (Item 1061, black lettering on white background, 8-1/2” x 11”) is located in close proximity to the electrical panel board and includes:

 

  • manufacturer’s name and address
  • model
  • serial number
  • year of manufacture
  • Fuel type
  • Complete Electrical Rating
  • A list of appliances that are factory installed
  • Ground snow load and roof design snow load
  • Thermal resistance of insulation and the outside design temperature used in heat-loss calculations
  • The Building Codes met by the building
  • Additional markings as may be required

 

2. QAI label with 'C' identifier (Item 1093) - Relocatable Commercial/Industrial Structures - Alberta Plumbing and Gas Compliance Label (Alberta Part 10 Program)

 

3. QAI Label with 'C' identifier (Item 1094) - Relocatable Commercial/Industrial Structures - Alberta Electrical Compliance Label (Alberta Part 10 Program)

 

4. QAI Label with 'C' identifier (Item 1095) - Relocatable Commercial/Industrial Structures - A277 Compliance Label

 
       
  Models:

The scope of buildings covered by this Listing include:

Buildings are:             Commercial/Industrial structures comprised of single or multiple modules. Structures are classified under Group C & D occupancy in a single storey configuration and without sprinkler systems. Buildings with sleeping accommodation have a building area not exceeding 600m2 and buildings without sleeping accommodation have a building area not exceeding 1200m2.

Structural:                  Conventional wood frame construction

Electrical Rating:         120/240 VAC, 60Hz, 600A max

Heating/Ventilation:     Exterior wall mounted forced air furnaces. Units to be Electric only. Systems may be equipped with air conditioning.

Plumbing:                   Conventional drainage and vent systems to a maximum of 240 hydraulic fixture units. 

Commercial/Industrial structures described above typically include but are not limited to office space and construction camp facilities, such as portable washroom trailers, dining trailers, and other similar commercial or industrial buildings.

This listing does not include vehicular lighting or break wiring systems.

Structures included in this listing are relocatable commercial/industrial structures manufactured at a central facility complete with electrical wiring, for installation to other modules in the field. These units, when completely assembled on site, are equipped with normal facilities for connection to electrical and plumbing services. QAI certification covers the construction of the structures and any factory installed electrical and plumbing services, and is intended to obviate the necessity of further inspections by the local regulatory authorities except for site connections to services or to other modules and for site mounting features.

 
 
       
  Note:

Structures are built to conform to CSA Standard A277, Alberta Building Code (Part 9 & 10), National Building Code (Part 9), National Plumbing Code (as applicable) and Canadian Electrical Code (Part 1).

Interconnection of modules, completion of structural systems and connection to services must be finished on site as specified in the electrical and building permits and are subject to inspection by the local authorities having jurisdiction.

Products shall be installed in accordance with the local code of the authority having jurisdiction.

 
 
 
 