  BUILDING PRODUCTS LISTING PROGRAM  
  Class: Structural Insulating Panels  
       
  Customer: Modus Structures Inc.  
  Location: Crossfield, Alberta  
       
  Listing No.: B1038-1  
  Effective Date: June 16, 2011  
  Last Revised: June 16, 2011  
  Expires: N/A  
       
  Standards:

The following standards as applicable and described in the tables below:

 

ASTM E72            Standard Test Methods of Conducting Strength Tests of Panels for Building Construction

ASTM E96            Standard Test Methods for Water Vapor Transmission of Materials

ASTM E564           Standard Practice for Static Load Test for Shear Resistance of Framed Walls for Buildings

ASTM E90            Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements

ASTM E119           Standard Test Methods for Fire Tests of Building Construction and Materials

ASTM E84            Standard Test Method for Surface Burning Characteristics of Building Materials

CAN/ULC S101      Standard Methods of Fire Endurance Tests of Building Construction and Materials

 
 
       
  Product:

Structural Insulating Panels in the following configurations:

Floor Panel:    FP95-16OC

Wall Panel:     WP6-WC

Roof Panel:     RP11875-16OC

Roof Panel:     RP14-12OC

 
 
       
  Markings:

Each structural insulating panel is marked with the following content, using a permanent adhesive label, in an area that is readily visible for inspection at the construction site: 

  1. Listee name or recognized trademark (Modus)
  2. City and province of manufacture (Crossfield, Alberta)
  3. QAI logo with ‘c’ and ‘us’ indicators
  4. Date of manufacture
  5. Product model
  6. QAI file number (B1038-1)
 
 
       
  Models:

 

FP95-16OC

 

WP6-WC

 

RP11875-16OC

 

RP14-12OC

ASTM E72

Transverse Load

450 psf (4’ x 13’)

181 psf (4’ x 21’)

257 psf (4’ x 8’) load on interior

293 psf (4’ x 8’)

Load on exterior

143 psf (4’ x 10.5’)

Load on interior

150 psf (4’ x 10.5’)

Load on exterior

288 psf (4’ x 24’)

421 psf (4’ x 24’)

ASTM E72

Axial Load

-

28,240 lbf (4’ x 8’)

26,376 lbf

(4’ x 10.5’)

-

-

ASTM E96

Water Vapor Transmission

-

0.088 perms with joint adhesive

0.103 perms without joint adhesive

-

-

ASTM E564

Racking Shear Load

-

7164 lbf (4’ x 8’)

6140 lbf (4’ x10.5’)

-

-

ASTM E90

Sound Transmission Loss

-

STC = 19

OITC = 21

-

-

ASTM E119

Fire Tests

60-minute fire resistance rating

load bearing 30psf.

 

Design #: B1038-FP9516OC-60min-30psf

60-minute fire resistance rating

Load bearing 1100 lbs / linear ft room side fire exposure.

 

Design #: B1038-WP6WC-60min-1100lbs/ft

60-minute fire resistance rating

load bearing 113psf

 

Design #: B1038-RP1187516OC-60min-113psf

-

ASTM E84

Surface Burning Characteristic

Flame Spread = 5

Smoke Developed Index = 400

CAN/ULC S101

Fire Endurance Tests

60-minute fire resistance rating

load bearing 30psf.

 

Design #: B1038-FP9516OC-60min-30psf

60-minute fire resistance rating

Load bearing 1100 lbs / linear ft room side fire exposure.

 

Design #: B1038-WP6WC-60min-1100lbs/ft

-

-

 Note: “-” indicates the property was not tested for the product configuration

Design Number: B1038-WP6WC-60min-1100lbs/ft

Assembly Rating: 1 Hour Wall Assembly

Load Bearing at 1100 lbs per lineal foot

Room Side Fire Exposure

Load bearing wall assembly using Modus WP6-WC structurally insulated panels manufactured from:

1. 26 gauge steel skin

2. Expanded polystyrene (EPS), Type 1, 6 in. thick

3. 18 gauge steel hat channel

4. Air space

Assembly requirements:

5. Two layers of Type X gypsum wallboard applied to the fire side.  One layer of 5/8 in. type X gypsum wallboard installed vertically with joints staggered 24 in. from panel joints.  Second (outer) layer composed of 1/2 in. Type X gypsum wallboard installed vertically with panel joints staggered 12 in. from base layer gypsum joints.  Each layer fastened with drywall screws located 16 in. on centre vertically and 16 in. on center horizontally.  Wallboard joints taped and filled. 

Connection of panels (not shown):

Panel joints are connected using eleven screws, located 12 in. on centers in each joint, on each side of the wall.  Panel joints are caulked with 3M CP25 WB+ on each side of the wall as an air seal in the joint.  The panel is oriented with the steel hat channel side towards the fire. 

Design Number: B1038-FP9516OC-60min-30psf

Assembly Rating: 1 Hour Floor Assembly

Load Bearing 30 psf

Fire resistance rating applies to room interior side only

Load bearing floor assembly using Modus FP95-16OC structurally insulated panels manufactured from:

1. 26 gauge steel skin

2. Expandable polystyrene (EPS), Type 1, 11-7/8 in. thick

3. Wood I-Joists, 11-7/8 in. height, spaced 16 in. on center

Assembly requirements:

4. Two layers of 1/2" Type C gypsum wallboard on the room side.  The wallboard is oriented perpendicular to the wood I-joists, with seams staggered 12” between layers.  Both layers of gypsum wallboard are mechanically fastened to the internal I-joists using 1-5/8” long coarse thread drywall screws spaced 8” on center at joints and 12” on center in the field.  All exposed joints are covered with joint tape and 2 coats of joint compound; all exposed screw heads are covered with two layers of joint compound.

5. 2” thick expanded polystyrene foam layer is adhered to the Modus panel surface using a two part adhesive (Weather-Tite® One Step Foamable Adhesive, WTT Systems), with continuous beads 6” apart.

6. 1/4” sheets of Densdeck black and white exterior gypsum substrate adhered to the exposed expanded polystyrene surface using a 2 part adhesive (Weather-Tite® One Step Foamable Adhesive, WTT Systems), with continuous beads 6” apart.

 

Connection of panels (not shown):

Panels are joined using tongue and groove connections with a continuous bead of air sealant applied to the female groove.  2” x 2” x 3/4" galvanized steel angle is fastened to the panel ends to provide a means for attaching rim board.  The angle is fastened to the steel panel skin using #6 x 1/2” wafferhead TEK point screws, nominally 8” on center.  Two layers of 3/4" thick rim board are fastened through the galvanized angle.  The first layer was attached using #10 x 2” wood screws placed 12” on center.  Two beads of PL400 panel adhesive are applied to the face of the rim board.  The second layer of rim board is fastened to the first using #10 x 2” wood screws spaced 12” on center.  The other edges of the assembly receive two layers of rim board, installed identically as the other ends except the base layer is attached to the top and bottom chord of the embedded joists using #10 x 3” wood screws.

installed identically as the other ends except the base layer is attached to the top and bottom chord of the embedded joists using #10 x 3” wood screws.

 
       
  Note:

Refer to QAI evaluation report B1038-1 and the applicable test reports for test assembly configurations used for fire endurance testing.  

Final acceptance of the product in the intended application is to be determined by the authority having jurisdiction (AHJ).

 
 
 
 
 
  The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.

No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.

Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.

 
   

Copyright QAI Laboratories, 2011