Icynene, Inc.
Building Products Listing Program
- Icynene, Inc.
- Thermal Insulation
- Mississauga, Ontario, Canada
- B1056-1
- B1056-1
- November 6, 2014
- March 30, 2017
- N/A
-
ASTM E84 “Standard Test Method for Surface Burning Characteristics of Building Materials” CAN/ULC S102 “Method of Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies”. ASTM E119 “Standard Test Methods for Fire Tests of Building Construction and Materials”. CAN/ULC S101 “Standard Test Methods for Fire Tests of Building Construction and Materials”. NFPA 285 “Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components”. Product:
Spray applied polyurethane foam insulation of the following models;
Icynene Product Icynene Model No. Patriot Spray Foam, Inc.
Product
Classic LD-C-50™ N/A Classic Max LD-C-50™ V2 Patriot 500 HY Classic Max Select LD-C-50™ V2.4 Patriot 500 Classic Plus LD-C-70™ N/A Classic ECO LD-R-50™ N/A Pro Seal MD-C-200™ V3 Patriot 200 Pro Seal ECO MD-R-210™ Patriot 200 ECO -
Spray applied polyurethane foam insulation
-
The following outlines Icynene Inc. spray applied polyurethane foam insulation performance determined in accordance with the noted standards. The ratings outlined in the some of the tables below are achieved in assemblies that are defined in the QAI Design Listings.
ASTM E84 – Surface Burning Characteristics
Models
Maximum Density
Maximum Thickness
Flame Spread Index (FSI)
Smoke Development Index (SDI)
Classic
Classic Max
Classic Max
LD-C-50™
LD-C-50™ V2
LD-C-50™ V2.4
0.55 lbs/ft3
(9 kg/m3)
4”
(100 mm)
≤ 25
≤ 450
Classic Plus
LD-C-70™
0.77 lbs/ft3
(12 kg/m3)
Classic ECO
LD-R-50™
0.55 lbs/ft3
(9 kg/m3)
Pro Seal
MD-C-200™ V3
2.2 lbs/ft3
(35 kg/m3)
Pro Seal ECO
MD-R-210™
2.3 lbs/ft3
(37 kg/m3)
CAN/ULC S102 – Surface Burning Characteristics
Models
Maximum Density
Maximum Thickness
Flame Spread Index (FSI)
Smoke Development Index (SDI)
Classic
Classic Max
Classic Max Select
LD-C-50™
LD-C-50™ V2
LD-C-50™ V2.4
0.55 lbs/ft3
(9 kg/m3)
2” (50 mm)
40
275
Classic Plus
LD-C-70™
0.77 lbs/ft3
(12 kg/m3)
3” (75 mm)
50
110
Pro Seal
MD-C-200™ V3
2.2 lbs/ft3
(35 kg/m3)
2” (50 mm)
45
325
ASTM E119/CAN/ULC S101 – Non-loadbearing Walls and Partitions
QAI Design #
Models
Maximum Density
Maximum Thickness
Fire Endurance Period
Classic
LD-C-50™
0.55 lbs/ft3
(9 kg/m3)
6” (150 mm)
1 hour
Classic Max
LD-C-50™ V2
0.55 lbs/ft3
(9 kg/m3)
Classic Max Select
LD-C-50™ V2.4
0.55 lbs/ft3 (9 kg/m3)
Classic Plus
LD-C-70™
0.77 lbs/ft3
(12 kg/m3)
Classic ECO
LD-R-50™
0.55 lbs/ft3
(9 kg/m3)
Pro Seal
MD-C-200™ V3
2.2 lbs/ft3
(35 kg/m3)
6” (150 mm)
1 hour
Pro Seal ECO
MD-R-210™
2.3 lbs/ft3
(37 kg/m3)
6” (150 mm)
2 hour
Pro Seal ECO
MD-R-210™
2.3 lbs/ft3
(37 kg/m3)
6” (150 mm)
3 hour
ASTM E119/CAN/ULC S101 – Restricted*-loadbearing Wall
QAI Design #
Models
Maximum Density
Maximum Thickness
Fire Endurance Period
Classic
LD-C-50™
0.55 lbs/ft3
(9 kg/m3)
2-1/4”
(57 mm)
1 hour
Classic Max
LD-C-50™ V2
0.55 lbs/ft3
(9 kg/m3)
Classic Max Select
LD-C-50TM V2
0.55 lbs/ft3 (9 kg/m3)
Classic Plus
LD-C-70™
0.77 lbs/ft3
(12 kg/m3)
Classic ECO
LD-R-50™
0.55 lbs/ft3
(9 kg/m3)
*Restricted-Load Bearing – Load rating for this assembly was 1,805 pounds per stud
NFPA 285 – Exterior Non-loadbearing Walls
QAI Design # Models Maximum Density Maximum Thickness B1056-1g Classic LD-C-50™ 0.55 lbs/ft3
(9 kg/m3)
6”
(150 mm)
Classic Max LD-C-50™ V2 0.55 lbs/ft3
(9 kg/m3)
Classic Max Select LD-C50TM V2.4 0.55 lbs/ft3 (9 kg/m3)
Classic Plus LD-C-70™ 0.77 lbs/ft3
(12 kg/m3)
Classic Eco LD-R-50™ 0.55 lbs/ft3
(9 kg/m3)
Pro Seal MD-C-200™ V3 2.2 lbs/ft3
(35 kg/m3)
Pro Seal ECO MD-R-210™ 2.3 lbs/ft3
(37 kg/m3)
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.