Net Talon Security Systems Inc.
Windows & Doors Listing Program
- Net Talon Security Systems Inc.
- Fire Doors
- Fredericksburg, Virginia
- F452-1
- F452-1
- July 25, 2018
- July 29, 2019
- N/A
-
UL 10B Fire Tests of Doors Assemblies.
UL 10C Fire Tests of Doors Assemblies.
NFPA 252 Standard Methods of Fire Tests of Door Assemblies. -
20-minute rated Neutral & Positive Pressure Fire Doors without Hose Stream
-
20-MINUTE COMPOSITE CORE FIRE DOORS CATEGORY B
Minimum 1-3/4” Thickness:
Swing Type: Maximum Dimensions Panel Type: Latching: Width: Height: Single Swing 4’0”
(1219 mm)7’0”
(2134 mm)Flush
onlySingle point
(Mortised or Cylindrical)
(Surface Mounted exit devices)The above Category B Fire Doors are required to be installed with an approved Category G gasket listed for use with wood doors when used in positive pressure applications.
Limitations: (Review Machining and Manufacturing Specifications Reports for further details and figures)
Latch Sets (Listed and labeled for rated opening)
• Cylindrical Latches.
• Mortised Latch / Deadbolt assembly:
o Schlage L9080 Mortise Storeroom Lock.
Deadbolts (Listed and labeled for rated opening)
• Cylindrical Deadbolts:
o Located a minimum of 2-1/4” center-line to center-line from the latch cutout.
• Mortised Latch / Deadbolt assembly:
o Schlage L9080 Mortise Storeroom Lock.
Hinges (Listed and labeled for rated opening)
• Hinges as per NFPA 80, Table 6.4.3.1Fire Exit Devices (Listed and labeled for rated opening)
• Surface Mounted Vertical Rod Fire Touch Bar Exit Device, may be less bottom rod.
• Rim Type Fire Exit Devices.
Door Closers (Listed and labeled for rated opening)
• Surface Mounted Door Closers.
Surface Mounted Protection Plates
• Steel, brass, bronze, aluminum, PVC, or plastic laminate max 48” high.
Viewers (Listed and labeled for rated opening)
• Maximum size of 1” diameter.
• Viewers located a minimum 12” away from edges of doors and other hardware.
• Must be located in minimum 5/8” thick panel.
Door Bottoms Seals (Listed and labeled for rated opening)
• Surface mounted automatic door bottom.
Glass Lights (Listed and labeled for rated opening)
• Glazing kit:
o Maximum dimensions: 6-1/4” x 21-1/4” (W x H) clear opening.
o Maximum clear opening area: 133 in2.
Door Bottoms Seals (Listed and labeled for rated opening)
• Surface mounted automatic door bottom.Notes:
Refer to QAI evaluation report F452-1 and the applicable test reports for test assembly configurations used for fire endurance testing.
Refer to the See FD002 – Fire Door Guidelines
Final acceptance of the product in the intended application is to be determined by the authority having jurisdiction (AHJ).
Product is to be installed in accordance with the manufacturer’s published installation instructions by qualified installing personnel.
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.