UPONOR, INC.
Plumbing Listing Program
- UPONOR, INC.
- Cross-linked polyethylene PEX Piping, Fittings and Valves.
- Apple Valley, Minnesota
Northeast Hutchinson, Minnesota - P321-1
- P321-1
- August 28, 2012
- September 25, 2018
- N/A
-
ASTM E84 “Standard Test Method for Surface Burning Characteristics of Building Materials”. UL 2846 “Fire Test of Plastic Water Distribution Plumbing Pipe for Visible Flame and Smoke Characteristics”. CAN/ULC S102.2 “Method of Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies”. ASTM E119 “Standard Test Methods for Fire Tests of Building Construction and Materials”. CAN/ULC S101 “Standard Methods of Fire Endurance Tests of Building Construction and Materials”. UL 263 “Fire Tests of Building Construction and Materials”. ASTM E814 “Standard Test Method for Fire Tests of Penetration Firestop Systems”. CAN/ULC S115 “Standard Method of Fire Tests of Firestop Systems”. -
Cross-linked polyethylene PEX Piping, Fittings and Valves.
-
AquaPEX™ (natural, red, blue)
hePEX™ Pipe
helioPEX™ X2
RCW PEX™
Pre-Insulated PEX Pipe (AquaPEX™, hePEX™, helioPEX™, and RCW PEX™)
ProPEX™ EP Fittings
ProPEX™ EP MultiPort Tees
PEX rings
ProPEX™ EP Connectors
ProPEX™ CPVC Adapters and ValvesAll PEX tubing, connectors, angle stop valves, and other accessories (if sufficient space available) shall be permanently marked with the following content applied
to an area that is readily visible after installation: Manufacturers name or trademark
Model Name
Standard: ASTM E84; CAN/ULC S102.2
Flame Spread Rating < 25, Smoke Developed Rating < 50
Nominal Size
QAI Logo with ‘c’ and ‘us’ indicator on UPONOR PEX pipe products where appropriate.
Manufacturing Traceability Label – Production date code -
Rating(s):
The following outlines the performance of UPONOR pipe determined in accordance with the noted standards. The ratings outlined in the some of the tables below are achieved in assemblies that are defined in the QAI Design Listings.
ASTM E84 – Surface Burning Characteristics
Products Limitations Flame Spread Index Smoke Developed Index AquaPEX™ (natural, red, blue)1
hePEX™
helioPEX™ X2
RCW PEX™
ProPEX™ EP Fittings
ProPEX™ EP MultiPort Tees
PEX rings
ProPEX™ EP Connectors
ProPEX™ CPVC Adapters and
ValvesMaximum 3/4-inch nominal
diameter tubing; 18-inch minimum
spacing between adjacent runs of
tubing< 25 < 50 Maximum 3-inch nominal diameter
with maximum ½-inch wall
thickness pipe products and
accessories, installed with rated
½-inch pipe insulation2; No
spacing requirements between
adjacent runs.< 25 < 50 UL 2846 – Surface Burning Characteristics
Products Limitations Flame Propagation and
Optical DensityAquaPEX™ (natural, red, blue)1
hePEX™
helioPEX™ X2
RCW PEX™Maximum 4-inch nominal
diameter tubing, installed with
rated ½-inch fiberglass or
mineral wool pipe insulation with
FS rating of ≤ 25 and SDI rating
of ≤ 50. The test results are
limited to individual pairs of
water distribution pipes.Complies CAN/ULC S102 – Surface Burning Characteristics
Product Limitations Flame
Spread
RatingSmoke
Developed
IndexAquaPEX™ (natural, red, blue)1
hePEX™
helioPEX™ X2
RCW PEX™
ProPEX™ EP Fittings
ProPEX™ EP MultiPort Tees
PEX rings
ProPEX™ EP Connectors
ProPEX™ CPVC Adapters and
ValvesMaximum 1-inch nominal diameter
tubing; 18-inch minimum spacing
between adjacent runs of tubing.< 25 < 50 Maximum ½-inch nominal
diameter tubing;
No spacing requirements between
adjacent runs.< 25 < 50 Maximum 3-inch nominal diameter
with maximum ½-inch wall
thickness pipe products and
accessories, installed with rated
½-inch pipe insulation2; No
spacing requirements between
adjacent runs.< 25 < 50 Note 1: Different sizes corresponding to different colors of AquaPEX™, hePEX™ and helioPEX™ X2 are dependent on manufacturer’s availability
Note 2: List of approved pipe insulation providers:The following list of fiberglass insulation types (at minimum thickness of ½”) are approved for use with Uponor’s hePEX™,
AquaPEX™ and helioPEX™ X2 when installed with UPONOR fittings and valves to maximum sizes outlined in tables above.
The insulations noted must be Listed to ASTM C547 by an approved agency and are approved for use at the dimension
specified above.Insulation Flame Spread Rating Smoke Developed Index (according to ASTM E84 / CAN/ULC S102.2) Manson Alley-K
Armaflex Composite
Johns Manville Micro-Lok
Johns Manville Micro-Lok HP
Owens Corning Vapor Wick
Owens Corning Fiberglass
GLT Pipe and Tank
Knauf Earthwool Redi-Klad
Nomalock< 25 < 50 UL 263, ASTM E119, CAN/ULC S101 – Wall Assemblies
QAI Design # Wall Type: Wall Load: Fire
Endurance
Period:P321-1A Light Gauge Steel Stud Non-Load Bearing 1 hour P321-1B Wood Dimensional Lumber Stud Restricted Load Bearing P321-1G Light Gauge Steel Stud Non-Load Bearing 2 hour P321-1H Wood Dimensional Lumber Stud Non-Load Bearing UL 263, ASTM E119, CAN/ULC S101 – Floor/Ceiling Assemblies
QAI Design # Wall Type: Wall Load: Fire Endurance Period: P321-1C Concrete Restricted Load Bearing 2 hour P321-1D Concrete3 Restricted Load Bearing P321-1E Concrete/Steel Joist Load Bearing P321-1F Wood Joist Restricted Load Bearing 1 hour Note 3: Either a 1-1/2 Hour or 2 Hour Assembly
ASTM E814, CAN/ULC S115 – Firestop Assemblies
QAI Design # Product: Floor/Wall Type: Fire
Endurance
RatingP321-1I AquaPEX™ (natural, red, blue)1
hePEX™
helioPEX™ X2
RCW PEX™Concrete 2 hour FH P321-1J 2 hour FH
50Pa
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.