Acemar Triplex S.A.S. Inc.
Building Products Listing Program
- Acemar Triplex S.A.S. Inc.
- Fire Door Frames
- Largo, FL, USA
- F485
- F485-2 Edition 2
- July 12, 2023
- February 6, 2024
- N/A
-
CAN/ULC- S104 Standard Method for Fire Tests of Door Assemblies.
UL 10B Standard for Fire Tests of Door Assemblies.
UL 10C Standard for Positive Pressure Fire Tests of Door Assemblies. -
ACEMAR 20-MINUTE CATEGORY “C” FIRE-RESISTANT DOOR FRAMES
-
20-MINUTE CATEGORY C PROPRIETARY WOOD TYPE FIRE DOOR FRAMES:
Maximum sizes:
Swing Type:
Maximum Dimensions
Width:
Height:
Single Swing
64-5/8″ (1605mm)
8’-3/4” (2455 mm)
Pairs
Not Permitted
Double Egress
Not Permitted
Limitations:
•Permitted door types: Wood doors.
•Maximum frame leg depth: Equivalent to wall depth.
•Minimum frame leg thickness: 1-1/2″ (38 mm)
•Stop Thickness: 5/8’’ (16 mm)Hinges (Listed and labeled for rated opening)
•Surface mounted 4-1/2″ by 4-1/2″ ball bearing type.
•Mortised maximum 4-1/2″ by 4-1/2″ ball bearing type.
•Mortised invisible hinges (SOSS model 218).
•Mortised Spring HingesDoor Closers (Listed and labeled for rated opening)
•Residential Frame: Surface Mounted Permitted.
•Commercial Frame Minimum 6-1/2’’ (165 mm) Depth: Mortised Closers Permitted of Maximum 1-1/4’’ (31 mm) width x 22-1/2’’ (572 mm) length x 1-1/8’’ (29 mm) depth.Electric Raceway
•Permitted.Maximum Sizes Fire Rated Fixed Door Panel Sidelite:
Sidelite Type:
Dimensions
Max. Width:
Max. Height:
Min. Thickness:
Fixed Door Panel
19-5/8’’ (499 mm)
95-1/2’’ (2403 mm)
1-3/4’’ (45 mm)
Limitations:
Minimum Frame Width: 1-1/2 in (38 mm)
Maximum Frame Width: Equivalent to wall thickness
Frame Depth: Minimum 4-1/2 in. (115 mm)
Stop: 5/8 in. (16 mm)
Edge Seal: Category G Listed
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.