Acemar Triplex S.A.S. Inc.
Building Products Listing Program
- Acemar Triplex S.A.S. Inc.
- Fire Doors
- Largo, FL, USA
- F485
- F485-1 Edition 2
- July 12, 2023
- February 6, 2024
- N/A
-
CAN/ULC-S104
Standard Method for Fire Tests of Door Assemblies.
UL 10B
Standard for Fire Tests of Door Assemblies.
UL 10C
Standard for Positive Pressure Fire Tests of Door Assemblies. -
20-minute Fire-Resistance Rated Category B Neutral Pressure Doors
-
20-MINUTE WOOD FLUSH DOORS:
Minimum 1-3/4’’ (44.5 mm) ThicknessSwing Type:
Maximum Dimensions
Panel Type:
Latching:
Width:
Length:
Single Swing
41-3/8“
(1052 mm)
94-½”
(2403 mm)
Flush
Single Point
(Mortised or Cylindrical)
Use in positive pressure (UL 10C) applications, requires the use of a listed Category G gasket.
Limitations:
Latch Sets (Listed and labeled for the rated opening.
•Cylindrical Latches
oListed and labeled cylindrical lock sets.
•Mortised Locksets
oListed for use with 20-minute wood type doors.Hinges (Listed and labeled for rated opening)
•Surface mounted 4-1/2″ by 4-1/2″ ball bearing type.
•Mortised maximum 4-1/2″ by 4-1/2″ ball bearing type.
•Mortised invisible hinges (SOSS model 218).
•Mortised Spring HingesDoor Sweep (Listed and labeled for rated opening)
•Surface mounted permitted.
•Mortised automatic door sweeps permitted.Door Closers (Listed and labeled for rated opening)
•Surface Mounted Permitted.
•Mortised Closers Permitted of maximum 1-3/8’’ (35 mm) width x 23’’ (584 mm) length x 2-7/8’’ (73 mm) depth.Surface Mounted Protection Plates
•Max 12” high.Louvers
•Not permittedViewers (Listed and labeled for rated opening)
•Maximum size of 1” diameter
•Multiple viewers located a minimum of 12” on center.
•Viewers located a minimum 5-1/2” away from edges of doors.Glass Lights
•Not Permitted.Plant-Ons
•MDF or solid wood with specific gravity ≥ 0.44 @ 12% m.c. plant-on moldings may be applied to one or both sides of a door.
•Adhesive and/or mechanical fasteners with a maximum penetration of 3/4”
•Moulding may not be applied closer than 3-1/2” to edge of door or edge of hardware cutout.Door Bottoms Seals (Listed and labeled for rated opening)
•Surface Mounted Snap-In in dual durometer vinyl with bulb and fins or with all fins seals may be used.
•Cutout dimensions are restricted to 1” wide and 1-3/4” deep x full width of the door.Electric Raceway
•Not Permitted
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.