AG Doors Ltd.
Building Products Listing Program
- AG Doors Ltd.
- Fire Door Frames
- Port Coquitlam, BC
- F486
- F486 Edition 1
- July 16, 2025
- July 16, 2025
- N/A
-
UL 10B (2020)
Standard for Fire Tests of Door Assemblies.
UL 10C (2021)
Standard for Positive Pressure Fire Tests of Door Assemblies.
NFPA 252 (2022)
Standard Methods of Fire Tests of Door Assemblies
CAN/ULC-S104-15-R2020
Standard Method for Fire Tests of Door Assemblies.
-
AD Doors 20-minute positive pressure fire door frames.
-
20-MINUTE CATEGORY C ALUMINUM AND STEEL FIRE DOOR FRAMES:
Maximum sizes:
SWING TYPE:
MAXIMUM DIMENSIONS
HEIGHT:
WIDTH:
Single Swing
84 in.
(2134 mm)
36 in.
(914 mm)
Pairs
Not Permitted
Double Egress
Not Permitted
Limitations:
· Permitted door types:
20-minutes hollow metal fire door.
· Minimum frame depth:
5-1/8 in. (130 mm).
· Maximum frame leg depth:
Equivalent to wall depth.
· Latch sets:
Cylindrical lock.
· Hinges:
Three, 4-1/2” x 4 in. (114 mm x 102 mm) steel butt hinges.
· Intumescent:
Pemko HSS 1000-7 on the frame.
Edge Sealing:
Intumescent: Pemso HSS 1000-7 on the frame.Mulled Assemblies:
Not permitted.Electric Raceways:
Not permitted.Door Closer:
Surface mounted permitted.Installation:
• 1/2 in. gap between frame and opening.
o #12 x 3 in. self-tapping screws to secure the frame into opening.
– 1x through each hinge location.
– 1x through the latch catch plate.
o #10 x 1-1/2 in. self-tapping screws to secure the frame into opening.
– 1x through the jam 24 in. on center.
– Wood shims at each 24 in. on center screw location.Notes: Final acceptance of the product in the intended application is to be determined by the
authority having jurisdiction. The product is to be installed in accordance with the
manufacturer’s published installation instructions by qualified installing personnel.
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.