Amvic Corporation
Building Products Listing Program
- Amvic Corporation
- Insulating Concrete Forms (ICF)
- Toronto, Ontario
- B1061-2
- B1061-2 ED 3
- May 7, 2014
- January 4, 2023
- N/A
-
CAN/ULC-S717.1 “Standard for Flat Wall Insulating Concrete Form (ICF) Systems”. ASTM E2634 “Standard Specification for Flat Wall Insulating Concrete Form (ICF) Systems” CAN/ULC S701.1 “Thermal Insulation, Polystyrene, Boards and Pipe Covering”. ASTM C578 “Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation”. CAN/ULC S102.2 “Standard Method of Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies”. ASTM E84 “Standard Test Method for Surface Burning Characteristics of Building Materials”. ASTM E119 Standard Test Methods for Fire Tests of Building Construction and Materials”. CAN/ULC S101 “Standard Methods of Fire Endurance Tests of Building Construction and Materials”. UBC 26-3 “Room Fire Test Standard For Interior of Foam Plastic Systems”. -
AmDECK Insulated Concrete Floor Systems
AMVIC Standard Insulated Concrete Forms (ICF)
AMVIC Plus 3.30 Insulated Concrete Forms (ICF) -
Finished product is marked with a permanent label containing the following information:
a) Manufacturers name or recognized trademark
b) Product model designation.
c) Date of manufacture.
d) CAN/ULC-S102 Flame Spread Index and Smoke Developed Index (FSI ≤ 250, SDI ≥ 500), ASTM E84 Flame Spread Index and Smoke Developed Index (FSI ≤ 25, SDI ≤ 450)
e) CAN/ULC-S701.1 Type 2, ASTM C578 Type II
f) QAI logo shown here: -
AmDECK complies with CAN/ULC S701.1 as Type 2 thermal insulation, and per ASTM C578 as Type II thermal insulation.
AMVIC Standard ICF and AMVIC Plus 3.30 ICF comply with CAN/ULC S717.1 and ASTM E2634 as flat walled, insulated concrete forms of Type 2 (CAN/ULC S701.1) / Type II (ASTM C578) insulation.
The following outlines AMVIC products ratings to the noted standards:
AmDECK / AMVIC Standard / AMVIC Plus 3.30 ICF Type 2 Specifications per CAN/ULC S701.1:
PROPERTY SPECIFICATION Thermal Resistance
m2*oC/W at 25 mm ThicknessMinimum 0.70 Water Vapour Permeance
Ng/Pa*s*m2 at 25 mm ThicknessMaximum 200 Dimensional Stability
% Linear ChangeMaximum 1.5 Flexural Strength
kPaMinimum 240 Water Absorption
% VolumeMaximum 4.0 Compressive Strength
kPa at 10% DeformationMinimum 110 Limiting Oxygen Index
%Minimum 24 AmDECK / AMVIC Standard / AMVIC Plus 3.30 ICF Type II Specifications per ASTM C578:
PROPERTY SPECIFICATION Compressive Resistance
psi at Yield or 10% DeformationMinimum 15.0 Thermal Resistance
F*ft2*h/Btu at 1.00 Inch ThicknessMinimum 4.0 Flexural Strength
psiMinimum 35.0 Water Vapor Permeance
Perms at 1.00 Inch ThicknessMaximum 3.5 Water Absorption
% VolumeMaximum 3.0 Dimensional Stability
% Change DimensionsMaximum 2.0 Oxygen Index
% VolumeMinimum 24.0 Density lbs/ft3 Minimum 1.35 AmDECK / AMVIC Standard / AMVIC Plus 3.30 ICF Surface Burning Characteristics per CAN/ULC S102.2:
AMVIC COMPONENT DENSITY MAXIMUM THICKNESS FLAME SPREAD INDEX (FSI) SMOKE DEVELOPED INDEX (SDI) Expanded Polystyrene
(EPS Panel)22 – 29 kg/m3 100 mm Maximum ≤ 250 ≥ 500 AmDECK / AMVIC Standard / AMVIC Plus 3.30 ICF Surface Burning Characteristics per ASTM E841:
AMVIC COMPONENT DENSITY MAXIMUM THICKNESS FLAME SPREAD INDEX (FSI) SMOKE DEVELOPED INDEX (SDI) Expanded Polystyrene
(EPS Panel)1.35 – 1.80 lbs/ft3 4.0 Inches Maximum ≤ 25 ≤ 450 1Ceiling Measurement Only. This measurement is conducted through determination of flame spread index and smoke developed index with the removal of any contribution of molten materials ignited on the floor of the tunnel assembly.
AMVIC ICF Allowable Fastener Loads
FASTENER ALLOWABLE WITHDRAWAL ALLOWABLE LATERAL SHEAR lbs kg lbs kg #6 Type S Fine Thread Drywall Screw 27 12 55 25 #6 Type W Coarse Thread Drywall Screw 29 13 73 33 #8 Type W Coarse Thread Drywall Screw 35 16 85 38.5 AMVIC Plus 3.30 Allowable Fastener Loads
FASTENER ALLOWABLE WITHDRAWAL ALLOWABLE LATERAL SHEAR lbs kg lbs kg #6 Type S Fine Thread Drywall Screw 22 10 40 18 #6 Type W Coarse Thread Drywall Screw 24 11 43 19.5 #8 Type W Coarse Thread Drywall Screw 23 10.5 63 28.5 Number 8 Wood Screw 26 12 52 23.5 AMVIC Standard / Plus 3.30 ICF UBC 26-3 Configuration
Meets requirements with 12.7 mm (½ inch) thickness gypsum board complying with ASTM C1396, fastened with 41 mm (1-5/8 inch) length standard drywall screws at 305 mm (12 inches) on center vertically, 406 mm (16 inches horizontally) maximum spacing. Fasteners must be anchored into AMVIC Standard or AMVIC Plus 3.30 ICF web ties.
AMVIC Standard / Plus 3.30 ICF Fire-Resistance Rated Construction
QAI Design Listing B1061-2 AMVIC Standard / AMVIC Plus 3.30 Insulated Concrete Form (ICF) – CAN/ULC S101 / ASTM E119 3 Hour Load Bearing Fire-Resistance-Rated Wall Assembly1, 15 Minute Stay-In-Place-Rated Wall Assembly (CAN/ULC S101)1
(See pdf Attachment – QAI Design Listing B1061-2 AMVIC Standard)
Note:
Final acceptance of the product in the intended application is to be determined by the authority having jurisdiction.
Product is to be installed in accordance with the manufacturer’s published installation instructions by qualified installing personnel.
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.