International Fireproof Technology Inc (IFTI)
Building Products Listing Program
- International Fireproof Technology Inc (IFTI)
- Applied Fireproofing
- Irvine, CA
- B1117-4
- B1117-4
- March 17, 2019
- May 25, 2022
- N/A
-
ASTM E84 “Standard Test Method for Surface Burning Characteristics of Building Materials”.
UL 723 “Standard for Test for Surface Burning Characteristics of Building Materials”.
ANSI/NFPA No 255 “Standard Method of Test of Surface Burning Characteristics of Building Materials“.
ASTM E2768 “Extended Duration Surface Burning Characteristics of Building Materials (30 Min Tunnel Test) “.
CAN/ULC S102 “Standard method of test for Surface Burning Characteristics of Building Materials and Assemblies”.
CAN/ULC S126 “Standard Method of test for Fire Spread Underroof-Deck Assemblies”.
-
DC360 Fire Retardant Coating.
DC360 is an intumescent water based latex coating intended for application on wood-based products used in interior conditioned spaces to provide increased resistance to flammability and smoke development. -
Product is marked with labels or stamp supplied by IFTI to each container. The markings include:
• Manufacturer’s name, trademark, or other recognized symbol of identification
• Product model designation
• QAI File Number B1117
• Date of manufacture or date code on the label or stamp
• Flame Spread Index / Smoke Developed Index Rating• QAI logo shown here:
-
The following outlines DC360 coating ratings determined in accordance with ASTM E84:
SUBSTRATE
FLAME SPREAD INDEX (FSI)
SMOKE DEVELOPED INDEX (SDI)
APPLICATION (WET MILS)
Oriented Strand Board (OSB)
≤ 25
≤ 50
10
Pine Boards
≤ 25
≤ 50
10
Note: UL 723 and NFPA No 255 are equivalent and have the same ratings.
The following outlines DC360 coating ratings determined in accordance with ASTM E84 extended 20 Minutes (ASTM E2768):
SUBSTRATE
FLAME SPREAD INDEX (FSI)
SMOKE DEVELOPED INDEX (SDI)
FLAME FRONT*
APPLICATION (WET MILS)
OSB
≤ 25
≤ 50
≤ 5 ft
10
Pine
≤ 25
≤ 450
≤ 5.5 ft
14
The following outlines DC360 coating ratings determined in accordance with CAN/ULC S102:
SUBSTRATE
FLAME SPREAD INDEX (FSI)
SMOKE DEVELOPED INDEX (SDI)
APPLICATION (WET MILS)
Pine Boards
≤ 25
≤100
6
The following outlines DC360 coating ratings determined in accordance with CAN/ULC S126
SUBSTRATE
DC 360 APPLICATION (WET MILS)
APPROVED BUILT UP ROOF ASSEMBLIES1
Oriented Strand Board (OSB) or Plywood.
Minimum 13 mm (1/2 inch) thickness.
Minimum 0.254 mm (10 mils)
DC 360 is approved for use with any built-up roof system installed between structural member locations without limitation.
Note 1: Installation limitations for CAN/ULC S126 requires the substrates noted installed with parallel to truss joints along truss member locations for mechanical fastening. Perpendicular to truss joints do not require blocking. Substrate is to be inspected to ensure substrate is clean, dry and in good condition prior to DC 360 application. DC 360 to be applied at minimum 0.254 mm (10 mils) wet film thickness, at temperatures from 10C – 30C for substrate bond. Application is to cover wood sheathing joints with DC360 to create continuous coating surface
Uses: In field application, to installed wood framing and sheathing materials to reduce the Flammability and Smoke Development of various substrates. DC360 is designed for interior condition spaces. All surface preparation should be carried out in accordance with good painting practices. To only be applied and used in weather protected locations where substrate moisture content is below 18%. DC360 comes as a ready to use coating and must be thoroughly mixed before use. It can be applied with brush, roller or airless Sprayer. The mil thickness should to be checked during installation to ensure the minimum noted thickness are maintained
Design, Installation & conditions of Use: See Manufactures Approved Design and Installation Documents.
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.