Proscience Inc. DBA Glassopolis Specialty Glass
Building Products Listing Program
- Proscience Inc. DBA Glassopolis Specialty Glass
- Fire-Resistant Door Glazing Component
- Toronto, Ontario
- F458-1
- F458-1 Edition 1
- July 31, 2019
- October 10, 2024
- N/A
-
UL 10B (2020) Standard for Fire Tests of Door Assemblies
UL 10C (2021) Standard for Positive Pressure Fire Tests of Door Assemblies
NFPA 252 (2022) Standard Methods of Fire Tests of Door Assemblies
CAN/ULC S104-15 Standard Methods of Fire Tests of Door Assemblies
-
•Fire-Resistant Door Glazing Component rated for use with Neutral & Positive Pressure rated Category “A” and “B” Fire-Resistant Doors.
•Fire Rated Ceramic Glazing Assemblies with Security Coatings. -
All glazing shall be labelled with the following content applied to an area that is readily visible after installation:
1.Manufacturers name or trademark
2.Country of manufacture
3.QAI Component Logo with US Marking shown below for TEMP20 Glass
4.QAI Component Logo with C/US Marking shown below for Coated Ceramic Glazing Assemblies
5.QAI Listing File Number (F458-1)
6.Applicable Standards: UL 10B, UL 10C, NFPA 252, CAN/ULC S104 -
TEMP20 Glass – Glassopolis TEMP20 Glass complies with UL 10B, UL 10C, and NFPA 252 with the ratings and limitations outlined below
Product
Name
Door Skin Type
Door Core Type
Maximum
Fire-resistance Rating
6 mm (1/4”)
TEMP20 Glass
(see below for
max. dimensions)
Wood
Solid Wood
20 Minute
(no hose stream)
Steel
Hollow /
Steel Stiffened
20 Minute
(no hose stream)
Maximum Glass
Dimensions
Maximum Viewing Area Dimensions
Width
Height
Width
Height
908 mm
(35.75”)
2254 mm
(88.75”)
883 mm
(34.75”)
2229 mm
(87.75”)
Product is permitted for use in Insulated Glass Units (IGU) constructed with the use of a steel spacer. Each glass pane must be TEMP20 Glass of minimum 6 mm (1/4”) thickness.
Coated Ceramic Glazing Assemblies – Glassopolis Coated Ceramic Glazing Assemblies comply with UL10B, UL10C, NFPA252, and CAN/ULC S104 with the ratings and limitations outlines below.
Ceramic Glass Minimum Thickness
Approved Coatings
Maximum Coating Thickness
Maximum
Fire-resistance Rating
5 mm
(3/16”)
Madico LCL 2100 PS USR
585 µm
(0.023”)
90 Minute
5 mm
(3/16”)
3M S70 Security Film
175 µm
(0.007”)
90 Minute
The installation types and maximum sizes for use of these coatings on glazing assemblies can be seen in the following table.
Min Ceramic Glass Thickness
Application
Glazing Compound
Max Fire-Resistance Rating
Max Viewing Area Dimensions
Width
Height
Area
5 mm
(3/16”)
Doors Temp Rise & Non-Temp Rise
Fiberfrax tabe, closed cell PVC, Pemko FG3000S90
90 Minute
305 mm
(12”)
838 mm
(33”)
0.065 m2
(100 sq in)
5 mm
(3/16”)
Doors Non-Temp Rise
Fiberfrax tabe, closed cell PVC, Pemko FG3000S90
90 Minute
914 mm
(36”)
1930 mm
(76”)
1.77 m2
(2736 sq in)
5 mm
(3/16”)
Transom Lites, Side Lites, Windows
Fiberfrax tabe, closed cell PVC, Pemko FG3000S90
90 Minute
1930 mm
(76”)
1930 mm
(76”)
2.21 m2
(3422 sq in)
6.35 mm (1/4”)
Metal Doors
Pemko FG3000
45 Minute
864 mm
(34”)
2134 mm
(84”)
1.84 m2
(2856 sq in)
6.35 mm (1/4”)
Wood Doors
Pemko FG3000
60 Minute
305 mm
(12”)
2032 mm
(80”)
0.619 m2
(980 sq in)
6.35 mm (1/4”)
Metal Doors
Pemko FG3000
90 Minute
305 mm
(12”)
1168 mm
(46”)
0.356 m2
(552 sq in)
6.35 mm (1/4”)
Windows and Side Lites
Pemko FG3000
45 Minute
1219 mm
(48”)
2438 mm
(96”)
2.97 m2
(4608 sq in)
6.35 mm (1/4”)
Transom Lites
Pure silicone caulk or Norton V980
45 Minute
2438 mm
(96”)
914 mm
(36”)
2.23 m2
(3456 sq in)
6.35 mm (1/4”)
Doors, Window, Door Frame
Pure silicone caulk or Norton V980
45 Minute
1372 mm
(54”)
1372 mm
(54”)
0.836 m2
(1296 sq in)
6.35 mm (1/4”)
Doors
Pure silicone caulk or Norton V980
90 Minute
305 mm
(12”)
838 mm
(33”)
0.065 m2
(100 sq in)
Notes:
•Refer to QAI evaluation reports F458 and the applicable test reports for test assembly configurations used for fire endurance testing.
•Refer to the QAI FD002 – Fire Door Guidelines for general guidelines of fire door assemblies
•Final acceptance of the product in the intended application is to be determined by the authority having jurisdiction (AHJ).
•Product is to be installed in accordance with the manufacturer’s published installation instructions by qualified installing personnel.
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.