Specified Technologies Inc.
Building Products Listing Program
- Specified Technologies Inc.
- Penetration Firestopping
- Somerville New Jersey, 08876 USA
- F505
- February 13, 2026
- October 05, 2026
- N/A
-
CAN/ULC S115-2023 Standard Method of Fire Tests of Firestop Systems.
ASTM E814-13a (2017) Standard Test Method for Fire Tests of Penetration Firestop Systems. -
Specified Technologies Inc. (STI) firestopping products of the following model(s):
• SpecSeal® LCI Intumescent Sealant
• SpecSeal® SBR Firestop Block
• SpecSeal® SSW 1000EX WrapStrip -
QAI DESIGN: MODEL SUBSTRATE PENETRANT APPROVED INSTALL
(Pressure)RATING MINUTES ASTM E814 CAN/ULC S115 F T F T H A-1 Specseal® LCI Sealant Minimum 127 mm (5’’) Concrete Maximum 38 mm (1.5’’) PVC Pipe Walls
(50 Pa)– – 60 45 – Maximum 38 mm (1.5’’) SDR 9 PEX Tubing – – 60 – – A-2 Specseal® LCI Sealant Minimum 127 mm (5’’) Concrete Maximum 38 mm (1.5”) Schedule 40 PVC Pipe Walls
(50 Pa)– – 120 120 – Maximum 38 mm (1.5”) SDR 9 PEX Tubing – – 120 – – A-3 Specseal® LCI Sealant Minimum 127 mm (5”) Concrete Maximum 51 mm (2”) Schedule 40 PVC Pipe Walls
(2.5 Pa)– – 60 45 – Maximum 51 mm (2”) Schedule 40 PVC-XFR Pipe – – 60 45 – Maximum 51 mm (2”) Schedule 40 NAPSYS-HR PVC Pipe – – 60 15 – Maximum 51 mm (2”) SDR 11 Aquarise CPVC Pipe – – 60 45 – Maximum 51 mm (2”) SDR 11 CPVC Pipe – – 60 45 – Maximum 38 mm (1.5”) SDR 9 PEX Tubing – – 60 60 – Maximum 51 mm (2”) Aluminum EMT Tubing – – 60 – – A-4 Specseal® LCI Sealant Minimum 127 mm (5”) Concrete Maximum 51 mm (2”) Schedule 40 PVC Pipe Walls
(2.5 Pa)120 15 120 15 120 Maximum 51 mm (2”) Schedule 40 PVC-XFR Pipe 120 15 120 15 120 Maximum 51 mm (2”) Schedule 40 NAPSYS-HR PVC Pipe – – 120 60 – Maximum 51 mm (2”) Aquarise SDR 11 CPVC Pipe 120 120 120 120 120 Maximum 51 mm (2”) SDR 11 CPVC Pipe 120 120 120 120 120 Maximum 51 mm (2”) SDR 9 PEX Tubing – – 120 15 – Maximum 51 mm (2”) Aluminum EMT Tubing – – 120 – – A-5 Specseal® LCI Sealant Minimum 127 mm (5”) Concrete Maximum 38 mm (1.5”) Aluminum EMT Tubing Walls
(2.5 Pa)– – 60 15 – Maximum 51 mm (2”) Schedule 10 Steel Pipe – – 60 15 – A-6 Specseal® LCI Sealant Minimum 127 mm (5”) Concrete Maximum 38 mm (1.5”) Aluminum EMT Tubing Walls
(2.5 Pa)– – 120 15 – Maximum 51 mm (2”) Schedule 10 Steel Pipe – – 120 15 A-7 Specseal® SBR Block Minimum 127 mm (5”) Concrete Maximum 51 mm (2”) Aluminum EMT Tubing Walls
(2.5 Pa)120 – 120 – 120 Maximum 102 mm (4”) Schedule 10 Steel Pipe 120 – 120 – 120 Maximum 102 mm (4”) Type L Copper Tubing 120 – 120 – 120 Maximum 2/0 AWG Copper Conductor PVC Jacketed Aluminum Clad or Steel Clad 3C TEK Cable 120 – 120 – 120 A-8 Specseal® LCI Sealant and
SpecSeal SSW1000EX Wrap StripMinimum 127 mm (5”) Concrete 102 mm (4”) SDR 11 CPVC Pipe or Schedule 80 CPVC Pipe Walls
(2.5 Pa)– – 60 60 – 102 mm (4”) Aquarise SDR 11 CPVC Pipe – – 60 60 – Maximum 76 mm (3”) SDR 11 CPVC Pipe or Schedule 80 CPVC Pipe – – 60 30 – Maximum 76 mm (3”) Aquarise SDR 11 CPVC Pipe – – 60 30 – 102 mm (4”) SDR 11 CPVC Pipe or Schedule 80 CPVC Pipe – – 120 45 – 102 mm (4”) Aquarise SDR 11 CPVC Pipe – – 120 45 – Maximum 76 mm (3”) SDR 11 CPVC Pipe or Schedule 80 CPVC Pipe – – 120 120 – Maximum 76 mm (3”) Aquarise SDR 11 CPVC Pipe – – 120 120 – C-1 Specseal® LCI Sealant Minimum 114 mm (4.5”) Concrete Maximum 38 mm (1.5”) Schedule 40 PVC Pipe Floors/Ceilings
(50 Pa)120 45/60 120 45/60 120 Minimum 127 mm (5”) Concrete Maximum 38 mm (1.5”) Schedule 40 PVC Pipe Walls
(50 Pa)120 45/60 120 45/60 120 C-2 Specseal® SBR Block Minimum 114 mm (4.5”) Concrete Maximum 51 mm (2”) SDR9 PEX Tubing Floors/Ceilings
(50 Pa)120 – 120 – 120 Minimum 127 mm (5”) Concrete Maximum 51 mm (2”) SDR9 PEX Tubing Walls
(50 Pa)120 – 120 – 120 D-1 Specseal® LCI Sealant 1-Hour Gypsum Assembly Maximum 38 mm (1.5’’) PVC Pipe Walls
(50 Pa)– – 60 45 – Maximum 38 mm (1.5’’) SDR 9 PEX Tubing – – 60 – – D-2 Specseal® LCI Sealant 2-Hour Gypsum Assembly Maximum 38 mm (1.5”) Schedule 40 PVC Pipe Walls
(50 Pa)– – 120 120 – Maximum 38 mm (1.5”) SDR 9 PEX Tubing – – 120 – – D-3 Specseal® LCI Sealant 1-Hour Gypsum Assembly Maximum 51 mm (2”) Schedule 40 PVC Pipe Walls
(2.5 Pa)– – 60 45 – Maximum 51 mm (2”) Schedule 40 PVC-XFR Pipe – – 60 45 – Maximum 51 mm (2”) Schedule 40 NAPSYS-HR PVC Pipe – – 60 15 – Maximum 51 mm (2”) SDR 11 Aquarise CPVC Pipe – – 60 45 – Maximum 51 mm (2”) SDR 11 CPVC Pipe – – 60 45 – Maximum 38 mm (1.5”) SDR 9 PEX Tubing – – 60 60 – Maximum 51 mm (2”) Aluminum EMT Tubing – – 60 – – D-4 Specseal® LCI Sealant 2-Hour Gypsum Assembly Maximum 51 mm (2”) Schedule 40 PVC Pipe Walls
(2.5 Pa)120 15 120 15 120 Maximum 51 mm (2”) Schedule 40 PVC-XFR Pipe 120 15 120 15 120 Maximum 51 mm (2”) Schedule 40 NAPSYS-HR PVC Pipe – – 120 60 – Maximum 51 mm (2”) Aquarise SDR 11 CPVC Pipe 120 120 120 120 120 Maximum 51 mm (2”) SDR 11 CPVC Pipe 120 120 120 120 120 Maximum 51 mm (2”) SDR 9 PEX Tubing – – 120 15 – Maximum 51 mm (2”) Aluminum EMT Tubing – – 120 – – D-5 Specseal® LCI Sealant 1 Hour Gypsum Assembly Maximum 38 mm (1.5”) Aluminum EMT Tubing Walls
(2.5 Pa)– – 60 15 – Maximum 51 mm (2”) Schedule 10 Steel Pipe – – 60 15 – D-6 Specseal® LCI Sealant 2-Hour Gypsum Assembly Maximum 38 mm (1.5”) Aluminum EMT Tubing Walls
(2.5 Pa)– – 120 15 – Maximum 51 mm (2”) Schedule 10 Steel Pipe – – 120 15 D-7 SpecSeal SBR Block 2-Hour Gypsum Assembly Maximum 51 mm (2”) Aluminum EMT Tubing Walls
(2.5 Pa)120 – 120 – 120 Maximum 102 mm (4”) Schedule 10 Steel Pipe 120 – 120 – 120 Maximum 102 mm (4”) Type L Copper Tubing 120 – 120 – 120 Maximum 2/0 AWG Copper Conductor PVC Jacketed Aluminum Clad or Steel Clad 3C TEK Cable 120 – 120 – 120 D-8 SpecSeal SSW 1000EX Wrap Strip and Specseal® LCI Sealant 1 Hour Gypsum Assembly 102 mm (4”) SDR 11 CPVC Pipe or Schedule 80 CPVC Pipe Walls
(2.5 Pa)– — 60 60 – 102 mm (4”) Aquarise SDR 11 CPVC Pipe – – 60 60 – Maximum 76 mm (3”) SDR 11 CPVC Pipe – – 60 30 – Maximum 76 mm (3”) Aquarise SDR 11 CPVC Pipe – – 60 30 – 2 Hour Gypsum Assembly 102 mm (4”) SDR 11 CPVC Pipe – – 120 45 – 102 mm (4”) Aquarise SDR 11 CPVC Pipe – – 120 45 – Maximum 76 mm (3”) SDR 11 CPVC Pipe – – 120 120 – Maximum 76 mm (3”) Aquarise SDR 11 CPVC Pipe – – 120 120 –
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.





USA
Canada
Europe
China
S Korea