Superform Products, Ltd.
Building Products Listing Program
- Superform Products, Ltd.
- Insulated Concrete Forms (ICF)
- Pincher Creek, Alberta
Cincinnati, OH - B1051-1
- B1051-1, Edition 5
- July 25, 2012
- November 5, 2024
- N/A
-
CAN/ULC S717.1-17
Standard for Flat Wall Insulating Concrete Form (ICF) Systems.
ASTM E2634-18(22)
Standard Specification for Flat Wall Insulating Concrete Form (ICF) Systems
ASTM D1761-20
Standard Test Methods for Mechanical Fasteners in Wood and Wood-Based Materials.
CAN/ULC S701.1-17
Standard for Thermal Insulation, Polystyrene Boards
ASTM C578-23
Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation.
CAN/ULC S102.2-18
Standard Method of Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies.
ASTM E84-21a
Standard Test Method for Surface Burning Characteristics of Building Materials.
ASTM D2843-16
Standard Test Method for Density of Smoke from the Burning or Decomposition of Plastics
UBC-26-3-97
Room Fire Test Standard for Interior of Foam Plastic Systems
ASTM D635-22
Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position.
ASTM D1929-16
Standard Test Method for Determining Ignition Temperature of Plastics.
ASTM E119-20
Standard Test Methods for Fire Tests of Building Construction and Materials.
CAN/ULC S101-14
Standard Methods of Fire Endurance Tests of Building Construction and Materials.
UL 263-11
Standard for Fire Tests of Building Construction and Materials.
-
Superform Insulated Concrete Forms (ICF)
-
Product is marked with labels supplied by Superform. Products are marked in a permanent manner where it is readily visible after installation with the following:
a) Manufacturer’s name or trademark
b) Product model designation
c) Month and year of manufacture
d) QAI file Number: B1051-1
e) CAN/ULC S701.1 Type 2, ASTM C578 Type II
f) ASTM E84 FSI and SDI Rating (FSI < 25, SDI < 450)
g) CAN/ULC S102.2 FSI and SDI ratings (FSI < 210, SDI < 450).
h) QAI logo shown here: -
The following outlines Superform ICF test results determined in accordance with the noted standards.
Superform ICF complies with specifications for flat-walled ICF in accordance with CAN/ULC S717.1.
Superform ICF complies with specifications for flat-walled insulated concrete forms in accordance with ASTM E2634.
Superform ICF EPS and cross ties have spontaneous ignition temperature ≥ 650oF when evaluated in accordance with ASTM D1929.
Superform ICF cross ties have a rate of burning of CC2 when evaluated in accordance with ASTM D635.
Superform ICF cross ties have smoke density index < 75 when evaluated in accordance with ASTM D2843.
SUPERFORM ALLOWABLE FASTENER LOAD CAPACITIES PER ASTM E2634 AND CAN/ULC S717.1 FOLLOWING ASTM D1761
Fastener
Allowable Withdrawal
Allowable Lateral Shear
lbs
kg
lbs
kg
#6 Coarse Thread Drywall Screw, minimum penetration ¾ inch (19 mm) into Superform ICF Crossties.
52
24
115
52
#10 Coarse Thread Wood Screw, minimum penetration ¾ inch (19 mm) into Superform ICF Crossties.
48
22
126
57
#14 Coarse Thread Wood Screw, minimum penetration ¾ inch (19 mm) into Superform ICF Crossties.
57
26
135
61
16 Gauge ½ inch Crown Staple, minimum penetration 1 inch (25 mm) into Superform ICF Crossties.
9
4
12
6
SUPERFORM ICF TYPE 2 SPECIFICATIONS PER CAN/ULC S701.1
Property
Superform Specification
Thermal Resistance, m2*oC/W at 25 mm Thickness
Minimum 0.70
Water Vapour Permeance, Ng/Pa*s*m2 at 25 mm Thickness
Maximum 200
Dimensional Stability, % Linear Change
Maximum 1.5
Flexural Strength, kPa
Minimum 240
Water Absorption, % Volume
Maximum 4.0
Compressive Strength, kPa at 10% Deformation
Minimum 110
Limiting Oxygen Index, %
Minimum 24
SUPERFORM ICF TYPE II SPECIFICATIONS PER ASTM C578
Property
Superform Specification
Compressive Resistance, psi at Yield or 10% Deformation
Minimum 15.0
Thermal Resistance, F*ft2*h/Btu at 1.00 Inch Thickness
Minimum 4.0
Flexural Strength, psi
Minimum 35.0
Water Vapor Permeance, Perms at 1.00 Inch Thickness
Maximum 3.5
Water Absorption, % Volume
Maximum 3.0
Dimensional Stability, % Change Dimensions
Maximum 2.0
Oxygen Index, % Volume
Minimum 24.0
Density, lbs/ft3
Minimum 1.35
SUPERFORM ICF SURFACE BURNING CHARACTERISTICS PER CAN/ULC S102.2
Superform
Component
Density
Maximum Thickness
Flame Spread Index (FSI)
Smoke Developed Index (SDI)
Expanded Polystyrene
(EPS Panel)
22 – 29 kg/m3
100 mm
≤ 210
≥ 500
SUPERFORM ICF SURFACE BURNING CHARACTERISTICS PER ASTM E841
Superform
Component
Density
Maximum Thickness
Flame Spread Index (FSI)
Smoke Developed Index (SDI)
Expanded Polystyrene
(EPS Panel)
1.35 – 1.80 lbs/ft3
4.0 Inches
≤ 25
≤ 450
Note 1: Ceiling Measurement Only. This measurement is conducted through determination of flame spread index and smoke developed index with the removal of any contribution of molten materials ignited on the floor of the tunnel assembly.
Superform ICF Thermal Barrier Stay-in-Place (UBC 26-3) Configuration:
Meets requirements with ½ inch thickness gypsum fastened with 1-¼ inch (31 mm) length standard drywall screws at 12 inches (305 mm) on center spacing in the field, and 6 inches (152 mm) on center spacing around the perimeter. Fasteners must be anchored into Superform ICF web ties.
SUPERFORM ICF FIRE-RESISTANCE RATED ASSEMBLIES PER CAN/ULC S101, UL 263, ASTM E119 – WALL ASSEMBLIES
QAI Design #
Description:
Type:
Fire-Resistance Rating
Insulated Concrete Wall of minimum 6 inches (152 mm) concrete thickness
Load Bearing1
3-hours
Insulated Concrete Wall of minimum 6.5 inches (159 mm) concrete thickness
Load Bearing1
4-hours
Notes:
Final acceptance of the product in the intended application is to be determined by the authority having jurisdiction.Product is to be installed in accordance with the manufacturer’s published installation instructions by qualified installing personnel. Also see QAI CERUS-1001
-
Final acceptance of the product in the intended application is to be determined by the authority having jurisdiction.
Product is to be installed in accordance with the manufacturer’s published installation instructions by qualified installing personnel. Also see QAI CERUS-1001 -
QAI maintains ISO/IEC 17065 accreditations via the International Accreditation Service (IAS) for the United States and Canada. Typically, certifications under this accreditation do not require the Seal of a Professional Engineer in order to be accepted by the authority having jurisdiction. Should a Professional Engineer Seal be needed, please select from the highlighted States / Provinces that are available for this specific manufacturer’s file. If a specific State / Province is not available, you may email info@qai.org to request if a sealed document is available for that jurisdiction.
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.