Sioux Chief Manufacturing Company, Inc.
Building Products Listing Program
- Sioux Chief Manufacturing Company, Inc.
- Penetration Firestopping
- Kansas City, Missouri
- B1147
- B1147-1 Edition 1
- September 21, 2023
- September 21, 2023
- N/A
-
ASTM E814 “Standard Test Method for Fire Tests of Penetration Firestop Systems”.
CAN/ULC-S115 “Standard Method of Fire Tests of Firestop Systems”.
-
Sioux Chief Service Boxes
-
Sioux Chief Service Boxes are marked with the following information:
a) Manufacturer’s name
b) Product name
c) QAI Listing number (B1147)
d) QAI logo with ‘c’ and ‘us’ identifier
e) F, T, and H ratings per ASTM E814 / CAN/ULC S115. -
The following outlines the assembly and ratings of Sioux Chief Service Boxes:
QAI Design No. Assembly: Test Standard: Load Bearing F Rating: T Rating: H Rating1: B1147-1A Between Stud Dual ServiceBox™ with FireShield ASTM E814 Non-Loadbearing 1-hour 27-minutes 1-hour CAN/ULC-S115 Non-Loadbearing 1-hour 27-minutes 1-hour B1072-1B Between Stud Dual ServiceBox™ with FireShield ASTM E814 Non-Loadbearing 2-hour 1-hour 2-hour CAN/ULC-S115 Non-Loadbearing 2-hour 1-hour 2-hour B1147-1C Over the Stud Dual ServiceBox™ with FireShield ASTM E814 Non-Loadbearing 1-hour 27-minutes 1-hour CAN/ULC-S115 Non-Loadbearing 1-hour 27-minutes 1-hour B1072-1D Over the Stud Dual ServiceBox™ with FireShield ASTM E814 Non-Loadbearing 2-hour 1-hour 2-hour CAN/ULC-S115 Non-Loadbearing 2-hour 1-hour 2-hour B1147-1E Stacked Dual ServiceBox™ with FireShield ASTM E814 Non-Loadbearing 1-hour 34-minutes 1-hour CAN/ULC-S115 Non-Loadbearing 1-hour 34-minutes 1-hour B1072-1F Stacked Dual ServiceBox™ with FireShield ASTM E814 Non-Loadbearing 2-hour 58-minutes 2-hour CAN/ULC-S115 Non-Loadbearing 2-hour 58-minutes 2-hour B1072-1G Single ServiceBox™ with FireShield ASTM E814 Non-Loadbearing 2-hour 58-minutes 2-hour CAN/ULC-S115 Non-Loadbearing 2-hour 58-minutes 2-hour B1072-1H Single ServiceBox™ with FireShield ASTM E814 Non-Loadbearing 1-hour 34-minutes 1-hour CAN/ULC-S115 Non-Loadbearing 1-hour 34-minutes 1-hour Note 1: ASTM E814 does not use H-Rating to identify that the assembly passed the hose stream test. The hose stream test is a requirement to achieve an F-Rating.
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.