STF Building Solutions Inc. / Solutions Bâtiment STF Inc.
Building Products Listing Program
- STF Building Solutions Inc. / Solutions Bâtiment STF Inc.
- Exterior Insulation and Finish Systems
- Sherbrooke, QC
- B1045-1
- B1045-1
- April 30, 2012
- June 28, 2024
- N/A
-
CAN/ULC S101 “Standard Methods of Fire Endurance Tests of Building Construction and Materials”.
CAN/ULC S114 “Standard Methods of Fire Endurance Tests of Building Construction and Materials”.
CAN/ULC S134 “Standard Method of Fire Test of Exterior Wall Assemblies”. -
STF Exterior Insulation and Finish Systems
-
Product is labeled by STF Building Solutions Inc. include the following information:
-Manufacturer’s name (STF Building Solutions Inc.),
-Expanded Polystyrene Type (Type 1),
-QAIc logo
-Certified Standards
-Material identification lot number -
Models:
STF Premier MA
STF Elite MA
STF Premier MWRatings:
STF Stratum NC is classified as noncombustible, and complies with CAN/ULC S114.
The following STF Exterior Insulation and Finish Systems assemblies have been evaluated for use in noncombustible construction as outlined in Section 3.1.5.5 of the National Building Code of Canada through testing to CAN/ULC S134
Table 1. STF EIFS CAN/ULC S134 Certified Assemblies
QAI Design #
APPROVED SYSTEM
Heat Flux 3.5 m above Opening
(kW/m2)
Flame Spread Above Opening
(meters)
STF Elite MA
STF Premier MW STF Premier MA
< 35
< 5.0
Note1: See design listing B1045-1a for details regarding approved components and installation evaluated by QAI.
The following STF Exterior Insulation and Finish Systems assemblies have been evaluated for use for protection of exterior building face containing foam plastic insulation as outlined in Section 3.2.3.8 of the National Building Code of Canada through testing to CAN/ULC S101.
QAI Design #
APPROVED SYSTEM
FIRE ENDURANCE
OPENINGS
STF Elite MA
STF Premier MW STF Premier MA
15 Minutes
No Openings Developed.
Note2: See design listing B1045-1b for details regarding approved components and installation evaluated by QAI. All noted STF assemblies require installation with noncombustible STF Stratum NC component at thickness outlined in the noted QAI design listing
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.