Norbec Architectural Inc.
Building Products Listing Program
- Norbec Architectural Inc.
- Insulated Metal Panels
- Boucherville, Quebec, Canada
- B1096-1
- B1096-1 Edition 8
- December 14, 2016
- September 20, 2024
- N/A
-
CAN/ULC S102
Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies.
CAN/ULC S126
Standard Method of Test for Fire Spread Under Roof-Deck Assemblies.
CAN/ULC S138
Standard Method of Test for Fire Growth of Insulated Building Panels in a Full-Scale Room Configuration.
CAN/ULC S101
Standard Methods of Fire Endurance Tests of Building Construction and Materials.
CAN/ULC S134
Standard Method of Fire Test of Exterior Wall Assemblies.
ASTM E84
Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM D1929
Standard Test Method for Determining Ignition Temperatures of Plastic.
NFPA 285
Standard Fire Test Method for Evaluation for Fire Propagation Characteristics of Exterior Wall Assemblies Containing Combustible Components.
NFPA 259
NFPA 286
Standard Test Method for Potential Heat of Building Materials.
Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth.
-
NOREX-L, NOREX-H, NOREX-S, Norex-M, and Norex-IN Insulated Metal Panels (IMP) with Polyisocyanurate Core.
NOREX-L can be supplied with or without a factory-applied gasket to the IMP joint. The approved gaskets are available in polyvinyl chloride (PVC) or silicone. -
Each panel is marked with a permanent label containing the following information:
a) Manufacturer’s name or recognized trademark
b) Product name
c) Date of manufacture
d) QAI file number: B1096
e) CAN/ULC S102 / ASTM E84 Flame Spread Index and Smoke Developed Indices as noted in this listing.
f) QAI logo shown here: -
Models / Ratings:
NOREX IMP have the following ignition properties determined in accordance with ASTM D1929:
Ignition Properties
Flash Ignition Temperature:
≥ 600o+F (316oC)
Spontaneous Ignition Temperature:
≥ 800o+F (427oC)
NOREX IMP surface burning characteristics determined in accordance with CAN/ULC-S102:
Model(s)
Flame Spread Index
Smoke Developed Index
Thickness Maximum
mm (inches)
Density Max. kg/m3 (lbs/ft3)
NOREX-L, NOREX-H, NOREX-S, NOREX-M, NOREX-IN
(w/o Steel Skin)
≤ 5001
≤ 175
204
(8)
41.6
(2.6)
NOREX-L, NOREX-H, NOREX-S, NOREX-M, NOREX-IN
(Evaluated With Steel)
≤ 252
≤ 100
204
(8)
41.6
(2.6)
Note 1: Flame spread index determined in accordance with CAN/ULC S127 for the foam core without steel skins.
Note 2: The above assembly has been evaluated and found compliant for Protection of Foam Plastic in Combustible Construction as outlined in Section 3.1.4.2 of the 2015 National Building Code of Canada (NBC).
NOREX IMP surface burning characteristics complying with CAN/ULC S126:
Model(s)
Results
Thickness Maximum
mm (inches)
Density Max. kg/m3 (lbs/ft3)
NOREX-L, NOREX-H, NOREX-S,
NOREX-M,
NOREX-IN
Complies
204
(8)
41.6
(2.6)
NOREX IMP surface burning characteristics determined in accordance with ASTM E84:
Model(s)
Flame Spread Index
Smoke Developed Index
Maximum Thickness inches (mm)
Density Max. lbs/ft3 (kg/m3)
NOREX-L, NOREX-H, NOREX-S, NOREX-M, NOREX-IN
(w/o Steel Skin)
≤ 25
≤ 450
8
(204)
2.6
(41.6)
NOREX-L, NOREX-H, NOREX-S, NOREX-M, NOREX-IN
(Evaluated With Steel Skin)
≤ 25
≤ 100
8
(204)
2.6
(41.6)
NOREX IMP products ratings determined in accordance with CAN/ULC-S138:
QAI Design #
Model(s)
CAN/ULC-S138 Compliant Assembly
NOREX-L, NOREX-H, NOREX-S,
NOREX-M, and NOREX-IN
to maximum 204 mm (8 inches) thickness
Sprinklered Room Compliant when equipped with 68oC (155oF) activation temperature, pendant style listed sprinklers.
Fastener at top and bottom panels for panel connection are required. Corners treated with flashing, mechanically secured.
Silicone sealant applied at panel and ceiling joint intersections. Optional, between panels joints can contain factory applied PVC or silicone gaskets.
Note 3: The above assembly has been evaluated and found compliant per 2015 NBC Section 3.1.5.7 Factory-Assembled Panels Clause 1) for use in Non-Combustible Construction for buildings that are sprinklered, < 18 meters high, have no Group A Group B or Group C major occupancies, with the panel having no air spaces, and where panels are used in application where flame spread ratings 10 – 150 are required.
Flame spread rating of ≤ 25 is noted as NOREX with joint ratings determined per CAN/ULC S102.
NOREX IMP products ratings determined in accordance with NFPA 286:
Model(s)
NFPA 286 Compliant Assembly
Fastener at top and bottom panels for panel connection are required. Corners treated with flashing, mechanically secured.
Silicone sealant applied at panel and ceiling joint intersections is optional. Optional, between panels joints can contain factory applied PVC or silicone gaskets.
Note 4: The above assembly has been evaluated and found compliant with 2018 / 2015 IBC Section 2603.9 Special Approval, for installation without a code prescribed thermal barrier through compliant testing to NFPA 286 in an end use configuration.
NOREX panels products evaluated to CAN/ULC S134:
NOREX Panels CAN/ULC S134
QAI Design #
Model(s)
Maximum Thickness
Flame Spread
Heat Flux at 3.5 m
Maximum Density
kg/m3 (lbs/ft3)
NOREX-H
NOREX-L
NOREX-M NOREX-IN
8 inches (204 mm)
< 5.0 m
< 35 kW/m2
41.6
(2.6)
Note 5: The above assembly has been evaluated and found compliant for use as combustible cladding in non-combustible construction as required by Section 3.1.5.5 of the 2015 National Building Code of Canada.
NOREX panels evaluated to CAN/ULC-S101 10-minute stay in place when used as wall panels:
NOREX Panels CAN/ULC S101 10 Minute Stay in Place6
QAI Design #
Model(s)
Maximum Thickness
Maximum Duration
Openings
NOREX-H
NOREX-S
NOREX-L
NOREX-M NOREX-IN
204 mm
(8 inches)
10 minutes
No Openings Developed
Note 6: The above assembly has been evaluated and found compliant per 2015 NBC Section 3.1.5.7 Factory-Assembled Panels Clause 2) for use in Non-Combustible Construction for buildings that are < 18 meters high, have no Group B or Group C major occupancies, with the panel having no air spaces, and where panels are used in application where flame spread ratings 10 – 150 are required.
Flame spread rating ≤ 25 is noted as NOREX with joint ratings determined per CAN/ULC S102.
NOREX IMP products evaluated to NFPA 285:
NOREX Panels NFPA 285
QAI Design #
Model(s)
Maximum Thickness
Potential Heat of Combustion6
Maximum Density
lbs/ft3
(kg/m3)
NOREX-H
NOREX-L
NOREX-M NOREX-IN
8 inches (204 mm)
11,350 Btu/ft2
2.6
(41.6)
Note 6: Potential Heat of Combustion determined in accordance with NFPA 259.
The materials, products or systems listed in this directory have been qualified to bear the QAI Listing Mark under the conditions stated with each Listing. Only those products bearing the QAI Listing Mark are considered to be listed by QAI.
The standard herein listed is the currently accepted version within the relevant certification scheme, code or other requirements unless otherwise noted. Transition periods may apply. Upon request, QAI will provide information about the validity of any of its certifications.
No warrantee is expressed or implied, and no guarantee is provided that any jurisdictional authority will accept the Listing found herein. The appropriate authorities should be contacted regarding the acceptability of any given Listing.
Visit the QAI Online Listing Directory located at www.qai.org for the most up to date version of this Listing and to validate that this QAI Listing is active. Questions regarding this listing may be directed to info@qai.org. Please include the listing number in the request.